SPG power generation system, providing optimum performance, reliability, and versatility for stationery standby, prime power, and continuous duty applications. All generator sets are prototype tested, factory build, and production tested.
ISO8528 - This generator set has been designed to meet ISO 8528 regulation.
ISO 9001 - This generator set is manufactured in facilities certified to ISO 9001.
This generator set is available with CE certification
Enclosed product is tested according to EU noise legislation 2000/14/EC
Open Type | ||
---|---|---|
Dimensions (LxWxH) | mm | 3026 x 1550 x 1994 |
Dry Weight | kg | 3130 |
Sound Attenuated Type | ||
Dimensions (LxWxH) | mm | 4400 x 1560 x 2360 |
Dry Weight | kg | 4150 |
Voltage | Standby Rating (ESP) | Prime Rating (PRP) | Amp | ||
---|---|---|---|---|---|
kVA | kW | kVA | kW | ||
400/230 | 485 | 388 | 425 | 340 | 613 |
Standby Rating (ESP) : Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046.
Prime Rating (PRP) : Continuous running at variable load for unlimited periods with 10% overload for 1 hour in any 12 hour period. In accordance with ISO 8528, ISO 3046.
Manufacturer | Doosan | ||
---|---|---|---|
Model | P158LE | ||
Engine Power Output at rated rpm | kWm | 414 | |
HP | 555 | ||
No. of Cylinders and Build | 8 Cylinder V Type | ||
Engine Speed | rpm | 1500 | |
Aspiration and Cooling | Turbocharged and After Cooled | ||
Total Displacement | L | 14.6 | |
Bore and Stroke | mm x mm | 128 x 142 | |
Compression Ratio | 15,0:1 | ||
Governor | Electronic | ||
Fuel Consumption at full load | L/hr | 89.3 | |
Fuel Tank Capacity | Litre | 700 | |
Oil Capacity | Litre | 21 | |
Coolant Capacity | L | 88.5 | |
Radiator Cooling Air | m³ /min. | 410 | |
Air Intake - Engine | m³ /min. | 25.5 | |
Exhaust Gas Flow | m³ /min. | 78.3 |
Design | Brushless 4 poles | |
---|---|---|
Insulation System | Class H | |
Rotor | Single Bearing System, Flexible Disc | |
Exciter type | Electronic (AVR) |
Engine
Fuel water seperator filter
oil heater
Alternator
Anti-Condensation Heater
Over sized alternator
Main line circuit breaker
PMG excitation + AVR
Panel
Automatic synchronising and power control system (multi gen-set parallel)
Transition synchronization with mains
Remote annunciator panel
Remote relay otput
Alarm output relays
Charge ammeter
Earth fault, single set
Accessories
Automatic or manual fuel filling system
Manual oil drain pump
Low and high fuel level alarm
Residential silencer
Enclosure weather protective or sound attenuated
Duct adapter (on radiator)
Inlet and outlet motorised louvers
Inlet and outlet accoustic baffles
Trailer
Tool kit for maintenance
1500/3000 hours maintenance kit
Double wall chassis
Main Fuel Tank
Control supervision and protection panel is mounted on the genset base frame. The control panel is equipped as follows: